Chiller Tonnage Sizing & Capacity Calculator

Author: becky

Jul. 07, 2025

Chiller Tonnage Sizing & Capacity Calculator

We have developed and adopted numerous “rules of thumb” to assist our customers in their quest for cost effective, efficient industrial cooling solutions.  We have shared these “shortcuts” on pages on our site for your convenience.  We have an experienced team waiting to assist you with your specific requirements.  Please feel free to call or any specific needs and we will promptly reply to your request.

With competitive price and timely delivery, Huateng sincerely hope to be your supplier and partner.

Plug in the following three inputs into the calculator above to get the estimated chiller size you need for your application.

  • The incoming water temperature
  • The chill water temperature you require
  • The flow rate

Still not sure what chiller you need? We have an experienced team waiting to assist you with your specific requirements.  Please feel free to contact us with any specific needs or questions and we will promptly reply to your request.

General Industrial Chiller Sizing Formula

General Industrial Chiller Sizing Formula

Looking for another way to find the right chiller size for your industry and application? You can generally calculate it using this formula:

Contact us to discuss your requirements of Brine Chiller Units. Our experienced sales team can help you identify the options that best suit your needs.

  1. Calculate Temperature Differential (?T°F)
    • ?T°F = Incoming Water Temperature (°F) – Required Chill Water Temperature
  2. Calculate BTU/hr.
    • BTU/hr. = Gallons per hr x 8.33 x ?T°F
  3. Calculate tons of cooling capacity
    • Tons = BTU/hr. ÷ 12,000
  4. Oversize the chiller by 20%
    • Ideal Size in Tons = Tons x 1.2

If you follow these steps, you should have the ideal chiller size for your needs. Here’s an example of the formula in action:

Scenario: What size chiller is required to cool 40GPM from 70°F to 58°F?

  1. ?T°F = 70°F – 58°F = 12°F
  2. BTU/hr. = 40gpm x 60 x 8.33 x 12°F = 239,904 BTU/hr.
  3. Ton Capacity = 239,904 BTU/hr. ÷ 12,000 = 19.992 Tons
  4. Oversize the chiller = 19.992 x 1.2 = 23.
  5. A 23. or 25-Ton chiller is required

Industry-Specific Considerations

There also industry specific rules of thumb for chiller sizing depending on your application. Click the links below to see best practices for your industry:

  • Metal Finishing
  • Medical Chiller
  • Plastics Processing
  • Food Processing

Brine Chiller | PDF | Refrigeration - Scribd

Document Informationclick to expand document information

1) SSI offers multiple compressor brine chillers in various sizes from 15-44°F leaving brine temperature. They contain advantages like energy savings from more efficient part-load operation and balanced compressor wear. 2) A selection procedure is outlined involving determining entering/leaving brine temperatures, capacity, and cooling water temperature (for water-cooled models). Performance charts are used to select a chiller matching the requirements. 3) Dimensions and specifications are provided for water-cooled condenser sections of different chiller models.

If you are looking for more details, kindly visit Oxidation Chiller Manufacturer and Supplier.

22

0

Comments

0/2000

All Comments (0)

Guest Posts

If you are interested in sending in a Guest Blogger Submission,welcome to write for us!

Your Name:(required)

Your Email:(required)

Subject:

Your Message:(required)

0/2000