HVAC Duct Vibration Dampeners - Asbestos Fabrics in ...

Author: Alice

Nov. 28, 2024

HVAC Duct Vibration Dampeners - Asbestos Fabrics in ...

HVAC Duct Vibration Dampeners
Asbestos Fabric Duct or Pipe Wrap; Asbestos Vibration Dampeners & Asbestos at the Air Handler

  • POST a QUESTION or COMMENT about vibration dampers used in heating & air conditioning air duct systems

HVAC duct vibration dampeners.

huaneng Product Page

This article describes the vibration damper (vibration dampener or vibration isolator) connecting the air handler unit supply plenum to the building supply duct and cites cases of asbestos-containing air conditioning or heating duct work that could send asbestos fibers into building air.

This article also describes asbestos-fabric dampeners on old HVAC ductwork and explains the dampener (or "vibration damper") function, location, inspection, common defects, repairs.

Asbestos fabrics are still sometimes found in buildings at a variety of locations including as HVAC duct vibration dampeners, duct or pipe insulating wrap, electrical wire insulation, and in special applications as fireproof curtains or blankets. Here we give special attention to asbestos cloth fabric HVAC duct vibration dampeners or "vibration dampers":

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?

What is the Vibration Dampener Found on Air Handlers for Heating and Air Conditioning Systems?

The "vibration damper" [properly called "vibration dampener"] shown in this photograph and at the top of this page is a fabric or rubberized fabric flexible connection used to join the supply air plenum to supply ducts in a building.

On a vertical air handler with conditioned air leaving at the top of the unit, you may see this fabric joint at the supply plenum to which the building supply ducts are connected.

The purpose of the vibration dampener is simple: by providing a flexible link between the air handler itself (a possible source of noisy vibrations) and the building duct work, the installer is reducing the transmission of noise through metal ductwork into the rest of the building when the blower, furnace, or air conditioner are running.

Thanks to reader Kenneth Meichtry, Building Maintenance Superintendent at General Services Agency, San Luis Obispo County, CA,for pointing out that the correct term for the HVAC component we illustrate here is vibration dampener.

Definition of vibration dampener

A vibration dampener is a device designed to absorb rather than transmit vibration. In the case of heating furnaces and air conditioners, mechanical vibrations that occur in the air handler would be transmitted as annoying sounds throughout the building if a vibration dampener were not installed between the air handler unit itself and the metal ductwork to which it is connected.

It would be equally accurate and more descriptive to refer to this device as a vibration isolator since what it's doing is isolating vibration in the vibrating part to avoid transmitting the vibration and thus annoying noise to other parts of the HVAC system or into the building.

On an air handler system or "blower unit", a fabric, currently often made of rubberized material, is installed as the vibration dampener. Vibrations in the air handler move the fabric without being transmitted into the metal ductwork.

In these articles we may include the less correct term "vibration damper" because it is very widely used among HVAC trades workers and because we want online searches for this noise-reducing component to enable our article to be found using either term: vibration damper or vibration dampener.

An additional HVAC noise source is of course an absent vibration dampener or one that is improperly connected or constructed.

For example we observed an air handler connection to the supply duct trunk that had so little clearance space between the steel components that even though a vibration dampener had been squashed into that space, vibration and noise from the air handler was being transmitted to the duct system and into the building.

Asbestos & Other Defects in Air Handlers & Duct Work: Damaged Vibration Dampeners & More Air Handler Noises

Inspect the vibration dampener to see that it is intact, not torn or damaged. If the blower is running you may feel air leakage around the damper if it is damaged or not properly installed.

  • Look for tears or holes in the vibration dampener;
  • Look for separation between the vibration dampener and the air handler outlet or plenum
  • Look for separation or gaps between the vibration dampener and the air supply duct trunk to which it is joined

Note that air blowing out of leaks in the HVAC supply duct system as well as air blowing into leaks in the return duct system can be a source of noises in the system including hisses, whistles, etc.

Asbestos Textile Fabric Uses in Buildings

Asbestos Fabric in HVAC Ducts as Vibration Dampener Material

On older furnaces and some air conditioning systems you may see a white woven fabric used for the vibration damper material. It is possible that this material was made of asbestos fabric [better photos wanted].

Colors of asbestos vibration dampener cloth: 

 

If the vibration damper fabric is white or white-gray (un-coated asbestos fabric) or possibly silver (aluminized coated asbestos fabric) and woven of a coarse-woven fabric it may be an asbestos material, typically containing chrysotile asbestos fibers in a high percentage.

Look at the lower left corner of our close up photo of a silver-colored asbestos vibration damper at a warm air furnace (photo above right). See that little black round spot above the "D" in "Daniel" of our © notice?

That's where a technician has made a hole in the asbestos damper material in order to insert a thermometer to sense air temperature. The fibers released by such minor damage are probably below the limits of detection.

It is easy to distinguish asbestos fabric in the vibration dampener from other common damper materials which have been used as other fabrics are more finely woven (see photos on this page) and may be rubberized or coated canvas or on newer systems, vinyl-coated synthetic fabric.

Reports of actual asbestos lab tests of asbestos cloth vibration dampers confirms their composition:

The photograph of an asbestos cloth HVAC duct vibration damper shown at left, courtesy Jason Lee, was confirmed by Mr. Lee as containing 65% chrysotile asbestos.

OPINION-DF: Further testing or inspection may be in order, since if indeed asbestos material was used at this location, and especially if it is damaged, it could release asbestos fibers into building air.

Watch out: Do not tear, cut, or damage the asbestos-fabric material during your inspection.

 

If the vibration damper is missing, torn, leaky, or is made of asbestos, we recommend that it be replaced with modern materials.

In some cases it may be less costly to simply replace an asbestos-suspect vibration damper than to pay to have it tested.

However if you want to test the vibration damper fabric, look inside the return plenum to the inside of the fabric.

Often we can find an individual thread sticking up above the metal clamp securing the fabric to the metal plenum sides, easily clipped with no damage to the fabric itself.

Asbestos Fabric as Duct or Pipe Insulation

Our photograph above illustrates use of an asbestos textile as a duct wrap or pipe wrap.

 

 

Research Confirming use of Asbestos Fabric in HVAC Duct Dampeners

Illustration: Kazmierski's patent of a high temperature expansion joint or duct vibration dampener used in HVAC systems.

[Click to enlarge any image]

  • Andrews, John S. SILENCER for VENTILATION DUCTS [PDF] U.S. Patent 4,034,826, issued July 12, .

    Excerpt: The outer wall may be of rubber or plastic coated fabric such as asbestos cloth or glass fiber cloth.
  • Cheyney, Charles C. SOUND DEADENER [PDF] U.S. Patent 1,865,677, issued July 5, .

    Excerpts:

    My device comprises an open frame 10 having top and bottom walls 11 and 12, re spectively, and side walls 13. This frame is made of any suitable material such, for in stance, as asbestos, fiber, plaster, rock wool, or cork board, or any other suitable material which will have a deadening effect upon sound vibrations.

    The baffle members 15 may be made of any suitable material such as asbestos, felt, rubber or other suitable soft, non-metallic material which will absorb or deaden sound vibrations.
  • Edwards, Howard C. "Silencer having contiguous concentric layers of sound absorbent material." U.S. Patent 3,181,646, issued May 4, .
    Excerpt:

    Shell 212 is surrounded by a relatively tightly compacted layer 216 of sound absorbent material, which may be asbestos or glass wool.
  • Enlund, Helmer LF, and Enos V. Stanhope. "Sound and vibration isolation support." U.S. Patent 3,606,218, issued September 20, .
  • Fraguela-Formoso, José Ángel, José Luís Fernández-Soto, Pablo Fariñas-Alvariño, and Luís Carral-Couce. "Marine safety: Asbestos in the maritime industry." Dyna 83, no. 198 (): 205-212.

    Excerpt: &#; asbestos have been used extensively in acoustical applications. However, the health hazard associated with asbestos &#; of the duct linings were predicted using a bulk reacting duct lining &#;
  • Kazmierski Jr, John, Craig E. Thornton, John L. Ambrose, and Frederick S. Dmuchowski. HIGH TEMPERATURE EXPANSION JOINT [PDF] U.S. Patent 4,140,338, issued February 20, . at https://inspectapedia.com/hazmat/Kazmierski-Patent-US

    This is a use of asbestos fabric coated with aluminum, such as we find in HVAC duct dampers. This is NOT a drywall joint tape.

    Abstract:

    An expansion joint for duct work is disclosed, which comprises a pair of frames, spacer means extending outwardly from said frames, and a boot. The boot has five layers: an inner asbestos/aluminum/silica material, a fibrous insulation batt, a middle asbestos/aluminum material, a vapor barrier, and an outer asbestos/fluoroelastomer material.
  • Fraguela-Formoso, José Ángel, José Luís Fernández-Soto, Pablo Fariñas-Alvariño, and Luís Carral-Couce. "Marine safety: Asbestos in the maritime industry." Dyna 83, no. 198 (): 205-212.
  • French, David W. "Asbestos paper coupling." U.S. Patent 3,227,476, issued January 4, .

    This was an asbestos paper used at HVAC heating duct or pipe couplings.
  • Hamid, Mahmud. "On the application of mastic materials as panel vibration dampers to fan housings and ventilation ducts." ().
    Abstract:

    The Geiger and Complex Modulus standard methods used to obtain the damping properties of viscoelastic materials were compared. The tests, using both methods, are described for a number of available materials.

    The results are in good agreement. It was found that a uniform coating of the entire vibrating surface did not correspond to the highest damping efficiency.

    An equivalent circuit, based on electro-mechanical analogies, was derived. This circuit proved to be a powerful technique in the study of vibration damping, and some of its parameters were combined in a universal curve.

    One viscoelastic material was chosen for most efficient application to a ventilation-duct model. At one anti-node the velocity-amplitude was reduced by 78.9%.
  • Peck, Robert E. "Conduit construction." U.S. Patent 2,226,523, issued December 24, .

    Excerpt: Economy Heat transmission characteristics Tests were conducted on various sizes of onehalf inch thick asbestos ducts ...
  • Yocom, Alvin M., and D. Olier George. "Cork containing composite sheet material." U.S. Patent 2,584,959, issued February 5, .
    Excerpt:

    More particularly the present invention relates to composite material composed of at least one thickness or stratum of an asbestos-rubber composition and at least one thickness or stratum of a cork-asbestos-rubber composition.

...


ADVERTISEMENT


Reader Comments, Questions & Answers About The Article Above

Below you will find questions and answers previously posted on this page at its page bottom reader comment box.

Reader Q&A - also see RECOMMENDED ARTICLES & FAQs

On -02-06 by Anxious About my Possible-Asbestos Vibration dampener - can't get anyone to replace it

Re-posting from private :

I am hoping you could please give me some advice/direction. I cannot seem to get any advice or direction that is consistent regarding asbestos. We have a house built in the 60s.

The vibration dampeners in our HVAC system (both return and supply side) t have asbestos in them. I have 3 very young children and I am desperate to find out what the right thing to do is.

I have tried consulting 2 industrial hygienists and 2 remediation companies and one of the Industrial Hygienists said the vibration dampeners should be removed because over time fibers could be potentially released.

The other one said leave them. The one that said leave it said removing it has the potential to contaminate the house and release more fibers and that as long as we leave them alone they are fine.

One of the remediation companies said take it out the other said too risky to take it out. We did TEM testing because I am scared and wanted to see if asbestos fibers where in the air in the house.

There were no fibers seen on the test but apparently the testing only has a sensitivity of 15 s/mm2.

Another environmental specialist recommended annual testing as an alternative to removal but with TEM testing even if nothing showed on the tests wouldn't that miss many dangerous fibers?

Anyway, I have no idea what is safe to do in this situation but want to ensure my toddlers breathe clean air. - Anonymous, /02/06

@anxious about vibration duct dampener asbestos

I'm sure sorry that you've had all this worry and expense.

Unfortunately the handling of your question, a perfectly reasonable one, has gotten totally out of hand and run amok, with people pouring your money over the problem in part to reduce their risk.

All of what follows is my opinon:

A vibration dampener on some older HVAC equipment used an asbestos cloth. It's not highly friable but might release some asbestos fibers into the air stream, and if damaged, say by chopping or cutting, could release more.

It's not reasonable to have spent money on asking people nor on asbestos testing - the sum of all of that is bound to far exceed the cost of simply removing the whole dampener assembly.

The duct dampener assembly is basically a section of sheet metal or ductwork that includes the dampener fabric between two halves. Its removal is a mechanical operation. During this process the fabric should not be particularly disturbed nor damaged - no cutting, chopping, etc. is needed; it's the sheet metal trunk or duct section that contains the fabric that gets removed, as an entire assembly.

While the actual, practical risk of significant levels of asbestos fiber release from an un damaged dampener is probably extremely small, it's reasonable to simply ask an HVAC duct installer to remove the whole assembly intact and to replace it with a new one that uses a non-asbestos fabric - usually a rubber-coated canvas.

Separately at OTHER PEOPLE's MONEY we explain the risk of asking experts for advice but getting advice that spends your money to reduce their risk. A good deal for them and a bad one for you.

For peace of mind, if you like, after the old vibration dampener(s) has (have) been removed, you can have your duct system cleaned by damp wiping and HEPA vacuuming in the nearby ductwork and in the work area.

@InspectApedia Publisher,

Thank you very much for such a quick response. I really appreciate the information. I am going to make an appointment with an HVAC company to have the whole dampener assembly removed.

@Worried about asbestos fabric vibration dampener in ductwork,

Smart move. And we're happy to have been of help to you.

Now you could help us out, too:

1. let me know what the HVAC duct company charges. And watch out: don't let them see that you're frightened about this or the cost of the job might be unnecessarily increased.

2. take photos of the vibration dampener as installed,

and take a couple of photos of the dampener being removed, and a final one of the new one installed.

If you give me 3-4 high res photos I can use them to illustrate the procedure - which would certainly help other readers who are faced with the same worry. We'd use them while keeping you anonymous unless you prefer to be identified.

I did not have any luck getting an hvac company to do the work. The last one I contacted just wrote back "we appreciate the consideration for the project, but we respectfully decline" and another one wanted over $ dollars which at the time seemed really high.

I have an appt. with a 3rd hvac company one tomorrow. I also reached out to 3 well known remediation companies b/c at that price I figured mine as well have a licensed abatement company do it.

One actually said they also would pass because I should just leave them in. The two that will do it will cost about 4 thousand dollars but that is including TEM clearance air testing after as well so we are picking one today and just getting it done next week unless the appointment with the hvac company goes well tomorrow.

Most importantly in the meantime, since this was dragging out, I had the IH take another set of 8 asbestos TEM air samples.

Seven of the 8 samples were at the Non Detect level (less then 15 fibers per mm2 or less then . f/cc2 but one room showed asbestos levels in the air so I have to assume it must be from the vibration dampeners because other than tile in the hvac room which is never touched and in good condition we cannot figure out another possible source.

The result in the one room was 14 fibers per mm2 or . s/cc

So now I am scared and willing to pay a whatever high price for the removal, I am also wondering if until they can get these dampeners out my family should leave our house?

And then do we also need to get the whole house remediated once they do remove the dampeners?

The only advice I can get from anyone is the level found in our house is below the clearance level used after remediation and "no amount of asbestos is considered safe" but that our levels are below the clearance level but that's not actually a recommendation.

Thanks for any information. Sorry to go in to so much detail but I just am not well-versed in any of this and just want to do what is safest for my family.

On -03-07 by InspectApedia Publisher (mod) - trouble getting a contractor to replace our asbestos vibration dampener

@Vibration Duct Dampener Replacement Wanted

Please trust that the warning I give here is given with respect and concern for you, though you may not like what I have to say.

I suspect that you have become so scared about this relatively low-risk problem that contractors whom you're contacting get scared too - scared of their liability, which can be a more significant risk when dealing with a customer who they think is very nervous.

You've probably spent more already on asbestos tests than it should have cost to simply have an HVAC company replace the vibration dampener.

I would take another careful look at your asbestos test report, to be sure you've got it right: are you really finding 14 asbestos fibers per cubic millimeter? Could it not be per cubic meter? That's a huge difference.

And if the lab says that your airborne asbestos level is below the "clearance level" - that's the "pass" standard that would be applied following an asbestos remediation job and would be a place to STOP doing further asbestos removal/cleanup.

Remember that when you scare a contractor they're going to be sure to say to you just what they think avoids any liability.

Ask your asbestos test lab to

1. clarify the finding

2. tell you the risk assessment, with reference to acceptable exposure levels (PELs) such as given by this OSHA document

https://www.osha.gov/sites/default/files/publications/OSHA.pdf

Permissible Exposure Limit (PEL) for asbestosis 0.1 fiber per cubic centimeter of air as aneight-hour time-weighted average (TWA), withan excursion limit (EL) of 1.0 asbestos fibersper cubic centimeter over a 30-minute period.The employer must ensure that no one isexposed above these limits.

Remember that OSHA guidelines are for the workplace. There may not be the same guides for homes.

Then call some duct installers and in a totally calm, un-concerned voice just ask them to replace your old vibration dampener so that you can be "on the safe side".

If you haven't done so, take a look at OTHER PEOPLE's MONEY - to understand what happened with the contractor you scared away and the one who wants a huge sum.

A typical duct vibration dampener costs about $200. U.S. + installation cost

Keep us posted.

Daniel

I have a rubberized dampener in the plenum of my home. I want to put in a UV light as a disinfectant. Will the UV light destroy the dampening material?

@Patrick Butler,

Good question. The answer is - I don't know.

UV light does ozidize and break down some types of rubber much more quickly than others.

So let's identify the dampener in your HVAC system, its brand and model and start there by asking the manufacturer.

My GUESS is that while UV may break down the rubber over time, it's not likely to be a rapid nor substantial issue.

Hello,

We just moved into our house, and I noticed these two fabric dampeners on the supply side of the HVAC.

Is this asbestos?

If so, What's the best way to go about safely removing and replacing these? I don't want to release acerated asbestos into my duct or house.

Tj

Looks like it could be


Hi does this seem like it can possibly contain asbestos?

Mimi

Yes That vibration duct dampener fabric could be asbestos cloth;

What are the country and city of the building where this is installed and what is the age of the building and of its ductwork?

Stacy

The vibration dampener cloth shown in our photos is not friable. "Friable" means that you can crumble a material into dust by using simply your fingers to squeeze and smear it.

On -12-18 by Stacy - is asbestos cloth on a vibration dampener friable?

Is asbestos duct clot friable or non friable?

- Asbestos cloth is not friable

Asbestos cloth is not friable - as the definition of friable means that you can easily reduce a material to fine dust or powder simpy by rubbing it between a thumb and forefinger.

How do you repair the cloth instead of removing it

On a vibration dampener made of asbestos cloth I would prefer to remove and replace the whole dampener.

In an emergency, as a temporary repair, if I had to leave the dampener in place I'd cut a working size opening in the sheet metal and then bond another heat-resistant cloth over the interior of the dampener joint using cloth and metallic adhesive tape.

Even spraying the interior and exterior surfaces of the fabric with a spray paint sealant would be helpful in reducing any fiber release.

We have green, finely woven cloth as the vibration dampeners on the furnace in our crawlspace---it looks a lot like the cloth in the photos at the top of the page (where you can see a hand pulling the cloth)---is this ACM? If not, what material is being used?
Thanks!

More likely rubber-coated canvas

Thanks! So the green fabric would not be ACM? It says on the page that ACM fabric is easy to identify (white, gray, silver).

For more information, please visit furnace vibration damper.

Marc,

Truth is, no one can assert for sure what a material is based on a brief e-text. To know for certain if a fabric contains asbestos you'd need to test a sample using a certified ASBESTOS TEST LAB (you can search InspectApedia for that phrase to find certified asbestos testing companies). You wouldn't want to bet your money nor health on speculation.

Question: can a technician fix a bad vibration dampener on a noisy Amana system ?

(20 hours ago) Lynda said:
I have a new Amana 16 seer 2 stage split system. There is a vibration and a variable harmonic sound in the wall where the ground unit connects to the house. It has been insulated in the wall and strapped to a stud. Still noisy.

The tech can not fix it. Any ideas as to cause and repair? Thanks.

Reply:

Often careful use of a mechanics' stethescope can pinpoint a vibration source such as a bad motor bearing. Figure vibration is most likely coming from an electric motor - of which your outdoor unit has one or more compressors and a fan motor.


...

Continue reading  at WHITE NOISE & SOUND CONDITIONERS or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see these

Asbestos HVAC Duct Articles

Suggested citation for this web page

VIBRATION DAMPENERS at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.


Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to ASBESTOS HAZARDS

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.

Search the InspectApedia website

Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.

Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification
when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.
Our Comment Box is provided by Countable Web Productions countable.ca

Citations & References

In addition to any citations in the article above, a full list is available on request.


ADVERTISEMENT

HVAC FAQs: What Is a Damper HVAC?

Getting To Know Your HVAC Damper: Definition, Benefits, and FAQs

Published June 12, by Tony Spezza

 


As a homeowner, no one expects you to have an encyclopedia of knowledge about your HVAC system, which is why you probably heard the term &#;HVAC damper&#; before but had no clue what it was. 

Fortunately, AAA Heating and Cooling would be happy to get you up to speed on all the ins and outs of HVAC dampers. 

Along with providing excellent service, our extensive HVAC knowledge can hardly be contained. Here, we will explain what a damper HVAC is, discuss its benefits, and address any other questions you may have. 

Table of Contents

What Is a Damper HVAC?

A damper is a movable small valve or plate that controls the airflow in a building&#;s HVAC system. 

These mechanisms regulate temperature through a zoning system. Zoning systems divide your home heating and cooling into different zones, giving you more options to control your air climate and energy usage. 

Dampers monitor airflow, temperature, and humidity levels in your home while lowering or raising the zone&#;s temperature to your desired setting.

How Do Dampers Work?

Dampers control your home&#;s heating and cooling by opening and closing to limit one area while increasing it to the other. 

HVAC zone dampers come in two types, manual and motorized: 

  1. Manual dampers:

    These require the homeowner to twist a handle to regulate the airflow into a particular zone. 

  2. Motorized or automatic dampers:

    These dampers work with your programmable zoning system and function independently. Because it works in tandem with programmable thermostats and other

    HVAC control systems

    , it tends to be more convenient and energy-efficient for homeowners.

Benefits of HVAC Dampers

One of the main benefits of dampers is that they improve your HVAC system&#;s control over airflow, therefore resulting in various other benefits. 

Damper systems function differently than residential vent systems. Closing a vent on the floor or the wall will still allow air to travel through your ducts, thus wasting energy. HVAC dampers are located closer to the mouth of the distribution pipe, allowing them to regulate airflow as needed. 

By preventing air leaks, dampers may help lower energy bills while also: 

  • Reducing noise (from the HVAC system)

  • Saving energy 

  • Maximizing home comfort levels 

  • Lowering energy bills 

One study found that home zoning systems may reduce heating and cooling bills by up to 30 percent. If you are looking to increase energy efficiency and save on utility bills, it might be time to consider a residential zoning system. 

If you&#;re considering damper installation, AAA Heating and Cooling would love to help. 

Our expert HVAC contractors in Beaverton and Portland can help you choose the right solution for your home or business. We are a family-owned company that is dedicated to providing quality services, repairs, installations, and outstanding customer service.

With every job we are assigned, we make sure to consider all of the factors to help you make informed decisions.

Other Common Questions About HVAC Dampers 

Does Every HVAC System Have a Damper?

Not every HVAC system has dampers, but most do. 

However, the number of dampers in a home may depend on its size and the HVAC system. Some builders may not choose to install dampers in homes to cut costs. If you do not have dampers, don&#;t worry!

A trusted HVAC professional should be able to install them. They will consider the size of your ducts, the type of dampers required, how to zone your rooms properly, and more. 

AAA Heating in Cooling has provided reliable HVAC services to Portland and Beaverton communities for over 60 years. With an A+ Better Bureau Business (BBB) rating and commitment to high-quality products and services, no HVAC job is too little or too big for our team. 

If you&#;re in the Beaverton or Portland area and need dampers installed, contact our team to schedule an appointment today. 

Is It Okay To Close HVAC Dampers?

Yes! You can adjust your home&#;s temperature in various rooms by adjusting (opening/closing) your furnace&#;s dampers.

A manual HVAC damper contains a door that can be manually opened or closed to adjust airflow in a particular zone or room&#;s ductwork. To locate your dampers:

  • Locate the main duct trunks leading from the furnace

  • Look 2 to 6 feet off of the main trunk to easily identify your dampers 

Once you have located your dampers, you can use the handle on each to either close or open them. The handle should be perpendicular to the duct when closed and pointing down the duct when opened. Each damper is associated with a specific room, so it&#;s essential to identify and label them.

How Long Do Dampers Last?

The quality of the equipment, how frequently you run your HVAC unit, and whether you follow regular maintenance schedules can all affect the lifespan of your HVAC components. With proper maintenance, dampers can last around 20 years. 

AAA Heating and Cooling also offers seasonal HVAC maintenance plans that allow you to ensure your HVAC system is well-maintained without having to worry about it. A well-maintained HVAC system will extend its life and protect it from unexpected (and inconvenient) breakdowns. 

How Do You Know If an HVAC Zoning System Works For Your Home?

Some homes have dampers installed in every run, some have only a few, and some have none. 

HVAC dampers are good for any homeowner looking to save on their energy bills and increase their system&#;s efficiency. 

When Having an HVAC Zoning System Makes Sense

You may want to consider installing an HVAC damper and zoning system if you have:

  • A multi-level home:

    Since

    hot air rises

    , the upstairs rooms in your home may sometimes feel much warmer than the downstairs. An automatic dampening system might help you set different temperatures for the upstairs and downstairs of your home

    with one thermostat. 

  • A home with high ceilings:

    Homes with high ceilings may often experience trapped heat at the top. By using dampers to zone your HVAC system, you can increase your room&#;s temperature more frequently and circulate the air more strategically. 

  • A home with large windows:

    Sunlight

    can raise your home&#;s temperature in certain spots. A damper HVAC allows you to make rooms with large windows their own cooling zone to avoid uneven cooling. Then all the cooling power is sent to where it needs to be the most.

AAA Heating and Cooling has the industry knowledge to help efficiently coordinate and conduct your HVAC dampers installation. 

We will walk you through the installation process while suggesting other helpful HVAC tips that might save you money, enhance your system&#;s efficiency, extend your system&#;s lifespan, and improve your home&#;s comfort levels.

Do you have other HVAC damper questions that you don&#;t see mentioned above? Just contact one of our heating and cooling professionals; we would love to talk about HVAC!

AAA Heating and Cooling: Residential HVAC Service, Repair & Installation in Beaverton & Portland

Considering a zoning system? Looking to repair or upgrade your existing model? Curious to learn more about zone dampers?

AAA Heating and Cooling is at your service. 

We have proudly served the Beaverton and Portland area since . Over the years, we&#;ve collected extensive HVAC knowledge and used it to solve various heating and cooling issues. From installing dampers on your existing HVAC system to retrofitting systems in older homes, there is little we can&#;t do. 

If you need HVAC services and would like to join the ranks of our many satisfied clients, request an appointment today. 

For more types of active suspension systeminformation, please contact us. We will provide professional answers.

12

0

Comments

0/2000

All Comments (0)

Guest Posts

If you are interested in sending in a Guest Blogger Submission,welcome to write for us!

Your Name:(required)

Your Email:(required)

Subject:

Your Message:(required)

0/2000